Enhanced control strategy for MMC-based STATCOM for unbalanced load compensation
Paper in proceeding, 2014

Modular Multilevel Converters (MMC) technology is today one of the preferred technology in HVDC and large STATCOM applications due to modularity, fault tolerance and high efficiency, but the voltage balancing becomes very challenging, especially during negative sequence current injection as required for load unbalance compensation. This paper proposes an improved balancing strategy for the delta configuration to overcome this situation based on the injection of a third harmonic zero sequence current. Simulation results have proved the effectiveness of the proposal even where different switching losses and capacitor tolerance are taken in consideration.

Converter control

Static Synchronous Compensator (STATCOM)

HVDC

Multilevel converters

FACTS

Author

M. Nilves

Universidad de Sevilla

J. M. Maza

Universidad de Sevilla

J. M. Mauricio

Universidad de Sevilla

R. Teodorescu

Aalborg Universitet

Massimo Bongiorno

Chalmers, Energy and Environment, Electric Power Engineering

P. Rodríguez

UPC

2014 16th European Conference on Power Electronics and Applications (EPE'14-ECCE Europe), Lappeenranta, Finland, 26-28 August 2014